|

      
STANDARDS FOR THE
DESIGN, CONSTRUCTION, MAINTENANCE AND USE OF LABORATORY FUME HOODS
Authored by:
Chemical Hazards Use Committee &
The Department of Environmental Health and Safety
at the University of Massachusetts, Amherst
November 1998
ALL LABORATORY EXHAUST VENTILATION SYSTEMS DESIGNED,
CONSTRUCTED, MAINTAINED, AND USED AT THE UNIVERSITY OF MASSACHUSETTS
AT AMHERST SHALL COMPLY WITH THE SPECIFICATIONS AND STANDARDS SET FORTH
IN THIS DOCUMENT
POLICY
GOAL
INTRODUCTION
FUME HOOD DESIGN AND CONSTRUCTION
TESTING
FUME HOOD EXHAUST SYSTEMS AND BIOLOGICAL SAFETY CABINETS
USE OF LABORATORY HOODS
DECONTAMINATION AND REMOVAL OF FUME HOOD SYSTEMS OR BIOLOGICAL SAFETY
CABINETS
CONTRACTORS
WORKING WITH FUME HOODS AND ASSOCIATED FANS AND DUCTWORK
APPENDICES
- PUBLICATIONS
- DEFINITIONS
- PROCEDURES FOR TESTING NEW OR
RENOVATED FUME HOOD SYSTEMS
- PROCEDURES FOR TESTING ESTABLISHED
FUME HOOD SYSTEMS
- RESPONSIBILITIES FOR THE
PROPER OPERATIONAL USE OF FUME HOODS
- EH&S NOTIFICATION OF "OUT OF SERVICE" FUME HOOD
SYSTEM
Laboratory exhaust ventilation systems designed, constructed, maintained,
and used at the University of Massachusetts at Amherst shall comply with
the specifications and standards set forth in this document and in the
publications listed (see Appendix A). A failure
to meet these standards shall be referred to the Chemical Hazards Use
Committee.
New or renovated fume hood systems will be tested using the Procedures
for Testing New or Renovated Fume Hood Systems (Appendix
C). Fume hood systems in new or renovated laboratories that do not
meet the testing criteria and specifications will not be accepted for
use by Environmental Health and Safety and the University of Massachusetts
at Amherst.
Established fume hood systems will be tested using the Procedures for
Testing Established Fume Hood Systems (Appendix
D ). When a fume hood fails to meet acceptable performance requirements
the hood will be declared out of service. Fume hood systems that do not
meet these requirements must not be used. These systems will be evaluated
by Physical Plant and if necessary, Facilities and Planning. See
Appendix E for Responsibilities for the Proper Operation and Use of
Fume Hoods.
The intention of this document is to set a standard for the design,
construction, maintenance, and use of laboratory ventilation in order
to maintain acceptable air quality in the laboratory building and surrounding
areas. This standard outlines criteria for stack heights, exhaust exit
velocities, and design considerations that shall be considered and implemented
at the University of Massachusetts at Amherst. This document together
with design standards established by Facilities and Planning will determine
requirements for laboratory exhaust ventilation systems. These requirements
do not preclude adherence to good engineering practice and the Massachusetts
Building Code and standards referenced therein. These requirements will
be included in contract specifications for all future contracts submitted
by the University of Massachusetts at Amherst. The University will only
accept bids on future contracts which meet these specifications.
This standard will concentrate on the aspects of fume hood system design
and operation that are critical to protecting the health and safety of
faculty, staff, students, and visitors and also minimizing nuisance odors.
Properly designed systems function to capture contaminants from the work
area and disperse them in the outside environment. Exhaust stacks function
to release contaminants from the inside of a building in order to minimize
contaminant reentrainment. The critical design aspects of fume hood systems
that are discussed in this document are: the quality of the fume hood
enclosure, the quality and quantity of supply air provided to the fume
hood, face velocity of the fume hood, exhaust stack height, exit velocity
of air being exhausted from the stack. In addition, effluent dispersal
is contingent upon factors such as exhaust stack / air intake separation,
stack height, stack height plus momentum, topography of the building and
surrounding environment, and wind dynamics.
Although system performance depends heavily on the above design elements
it must be noted that the fume hood performance in a room is affected
by room layout and supply air distribution. System performance depends
on the fan and duct layout as well as fan type and discharge conditions.
These issues are dealt with in detail in the mechanical design standards
developed by Facilities Planning.
A fume hood that is appropriate for the purpose should be chosen. General
guidelines on types of hoods and their application are presented in the
Industrial Ventilation Manual (most current edition).
Laboratory fume hoods and associated exhaust ducts should be constructed
of non-combustible, nonporous material that will resist corrosion. They
should be equipped with vertical or horizontal sashes that can be closed,
air foils built into the fume hood at the bottom and the sides of the
sash opening, and baffles to attain a uniform face velocity under different
conditions of hood use. Combination horizontal and vertical sashes shall
be provided unless special conditions dictate otherwise. Additionally,
recognized good design and construction features are listed in ANSI/AIHA
Z9.5 1992.
Fume hoods should be tested before a hood leaves the manufacturer using
the ANSI/ASHRAE 110-1995 standard, Method of Testing Performance of Laboratory
Fume Hoods". ). All new hoods shall meet the ANSI/ASHRAE requirements
for Class 1 hoods including a tracer gas performance of AM(as manufactured)
0.05(parts per million) or better at a tracer gas release rate of 4.0
Liters per minute. Documentation shall be provided with the results of
the test. Performance is measured by specific tests:
- Flow visualization,
- Face velocity measurements,
- Test method for Variable-Air -volume (VAV) Fume Hoods,
- VAV Response Test , and
- Tracer gas containment .
Flow visualization qualitatively tests a hood's ability to contain vapors.
This test consists of a small local challenge (use of a smoke tube), and
a gross challenge (use of a smoke candle or smoke generator) to the hood.
Smoke is released in the hood to visually determine if a hood or associated
duct work leaks as it is actually used.
Face velocity measurements determine the average velocity of air moving
perpendicular to the hood face. The measurement is usually expressed in
feet per minute (fpm). Face velocities will often provide information
concerning the fume hood's ability to properly control contaminants.
A tracer gas leak test will quantitatively determine if the fume hood
is properly containing contaminants. A tracer gas is released in the hood
and a continuous-reading instrument is positioned outside the hood to
monitor for the escape of the tracer gas. The preferred tracer gas is
sulfur hexafluoride (SF6 ).
Each variable air volume hood shall maintain an average face velocity
of 90-110 fpm at the maximum allowed hood opening. Each constant volume
hood shall maintain an average face velocity of 90-110 fpm in the half
open position. A written request for an exception to this requirement
must be submitted to EH&S and will be granted only by EH&S. Face velocity
measurements are to be made with a recently calibrated mechanical or electrical
anemometer . Measurements should be made of 1 square foot areas across
the face of the hood and no single face velocity measurement should be
more than plus or minus 20% of the average. For further information, refer
to ANSI/ASHRAE 111-1988, Practices for Measurement, Testing, Adjusting,
and Balancing of Building Heating, Ventilation, Air-Conditioning, and
Refrigeration Systems.
All fume hoods shall include some means of monitoring face velocity
with a visual and audio alarm.
The proper volume, distribution, and quality of supply air shall be
provided to laboratories containing fume hoods. ANSI/AIHA Z9.5 1992 and
ANSI/ASHRAE 62 provide these standards. Make up air (replacement air)
should be equal to at least 95% of the volume exhausted from the laboratory.
This air shall not be recirculated from other laboratory areas. Although
laboratory supply air seldom requires air cleaning, ASHRAE ( HVAC Application
Handbook 1995) provides technical information for the reduction of contamination
from atmospheric dust and dirt.
Air supply systems for rooms containing chemical fume hoods shall not
create room air drafts at the face of any hood greater than one half (and
preferably one third) the face velocity of the hood. For most laboratory
hoods, this means 50 fpm or less terminal throw velocity at 6 feet above
the floor. ACGIH's "Industrial Ventilation - A Manual of Recommended Practice"
provides design criteria to help achieve these standards
Variable-air volume fume hoods shall be installed unless accepted design
practice dictates otherwise. A VAV hood is one that is fitted with a face
velocity control which varies the amount of air exhausted from the fume
hood in response to the sash opening to maintain a constant face velocity.
These hoods produce an acceptable face velocity over a relatively large
sash opening and also provide significant energy savings by reducing the
flow rate from the hood when it is closed.
Exhaust stacks shall be designed and built to prevent recirculation
of contaminated air from the fume hood exhaust system into the fresh air
supply of the facility or adjacent facilities. The effluent exhaust shall
escape the building envelope. The stack shall also provide significant
effluent dispersal so that effluent downwash does not occur at ground
level. They shall be designed and built with the latest applicable ASHRAE
standards and using ANSI/ASHRAE Z9.5. ASHRAE 1997 Fundamentals Handbook
and the publication "Laboratory Stack Height Determination and Evaluation
Methods" present three methods for specification and evaluation of stack
heights from laboratory hood exhaust fans.
Effluent discharge shall be:
- direct to the atmosphere (unless treated for recirculation).
- conform to federal, state, and local air emission regulations.
- released so that reentry of effluent from the discharging building
or a surrounding building is reduced to allowable concentrations inside
of the building.(Allowable concentrations shall be determined using
information on the nature of the contaminants to be released, recommended
industrial hygiene practice, and applicable safety codes.)
Exhaust discharge from stacks shall:
- be in a vertical up-draft direction at a minimum of 10 ft above adjacent
roof lines and located with respect to surrounding air inlets as to
avoid contaminant reentry.
- have a minimum exit velocity of 3000 fpm.
Recirculating or ductless fume hoods are not permitted for the removal
of chemical contaminants.
ANSI/AIHA Z9.5 1992 provides standards for non-traditional laboratory
fume hoods. These hoods include perchloric acid fume hoods, walk-in fume
hoods, and glove boxes. ACGIH's Industrial Ventilation Manual provides
information on perchloric acid fume hoods, biological safety cabinets,
and glove boxes. All class II biological safety cabinets must meet the
National Sanitation Foundation Standard Number 49 for Class II Biohazard
Cabinetry for design, manufacturing and testing.
All new and renovated fume hoods will be tested after installation and
before use. See Procedures for Testing New or Renovated Fume Hoods (Appendix
C)
All established fume hoods will be tested annually or more often if
problems occur. See Procedures for Testing Established Fume Hoods (Appendix
D).
The operational integrity of a new biological safety cabinets (BSC)
must be validated by certification before it is put into service or after
a cabinet has been repaired or relocated. In addition, it will be the
responsibility of the faculty member to have BSC tested and certified
annually. Certification will be performed by an accredited Biohazard Cabinet
Field Certifier using National Sanitation Foundation (NSF)Standard Number
49 for Class II Biological Safety Cabinets.(See Massachusetts Higher Education
Consortium list).
All personnel using fume hoods, biological safety cabinets, and glove
boxes will follow the policies and procedures outlined in University of
Massachusetts/Amherst Laboratory Health and Safety Manual. ANSI/AIHA Z9.5
1992 and ACGIH's Industrial Ventilation Manual provide additional work
practices to minimize emissions and employee exposure when working with
fume hoods.
CDC/NIH's publications Biosafety in Microbiological and Biomedical Laboratories
and Primary Containment for Biohazards: Selection, Installation, and Use
of Biological Safety Cabinets provide additional information on the use
of biological safety cabinets. Horizontal and vertical laminar flow clean
benches are not biological safety cabinets. These clean benches provide
a very clean environment for the manipulation of non-hazardous materials
and can be used for activities such as the dust-free assembly of sterile
equipment or electronic devices. Since the operator sits in the downstream
exhaust from the clean bench, this equipment must never be used for the
handling of toxic, radioactive, infectious, or sensitizing materials.
When a fume hood is scheduled for removal, the hood, fan, and associated
ductwork must be tested for the presence of radioactive materials and
hazardous chemicals eg. perchlorate salts, asbestos, oxidizers, sulfides,
cyanides, lead, and mercury. EH&S will determine the need for testing
and decontamination of the hood and ductwork. If decontamination is necessary,
fume hood(s) must be decontaminated before removal. Biological safety
cabinets must be decontaminated before removal or a move to a different
location. Costs associated with testing and/or decontamination shall be
included in the total project cost.
Before beginning work, all contractors and subcontractors, involved
with a renovation project involving fume hoods and associated fans and
ductwork must consult with EH&S for recommendations for training and personal
protective equipment for their employees.
ACGIH. "Industrial Ventilation- A Manual of Recommended Practice." American
Conference of Governmental Industrial Hygienists, Ed. 22, 1995, (or the
most recent edition)
Available from:
ACGIH
1330 Kemper Meadow Drive
Cincinnati, OH 45240
ANSI/ASHRAE 110-1995 "Method of Testing Performance of Laboratory Fume
Hoods." (1995). (or the most recent edition)
Available from:
ASHRAE
1791 Tullie Circle, NE
Atlanta, GA 30329
ANSI/ASHRAE 111-1988, Practices for Measurement, Testing, Adjusting,
and Balancing of Building Heating, Ventilation, Air-Conditioning, and
Refrigeration Systems, (or the most recent edition)
Available from:
ASHRAE
1791 Tullie Circle, NE
Atlanta, GA 30329
ANSI/AIHA. Z9.5 1992 "American National Standard for Laboratory Ventilation."
American Industrial Hygiene Association. 1992. (or the most recent edition)
Available from:
AIHA
2700 Prosperity Avenue
Suite 250
Fairfax, VA 22031
ASHRAE. "1997 Handbook- Fundamentals Volume" . American Society of Heating
and Air-Conditioning Engineers, Inc. 1997.(or the most recent edition)
Available from:
ASHRAE Customer Services
1791 Tullie Circle NE
Atlanta, GA 30329
ASHRAE. "1995 ASHRAE Handbook- Heating, Ventilating, and Air-Conditioning
Applications." American Society of Heating and Air-Conditioning Engineers,
Inc. 1995. (or the most recent edition)
Available from:
ASHRAE Customer Services
1791 Tullie Circle NE
Atlanta, GA 30329
Biosafety in Microbiological and Biomedical Laboratories. U. S. Department
of Health and Human Services. U. S. Government Printing Office. Washington,
D. C. 1993 (or most recent).
Laboratory Stack Height Determination and Evaluation Methods - Possible
Additions to the ANSI/AIHA Z9.5 Standard on Lab Ventilation. Ratcliff,
M. and Sandru, E. ASHRAE Winter Meeting. 1998
NFPA. Standard on fire protection for laboratories using chemicals.
Standard 45. National Fire Protection
Primary Containment for Biohazards: Selection, Installation, and Use
of Biological Safety Cabinets. U. S. Department of Health and Human Services.
U. S. Government Printing Office. Washington, D. C. 1995 (or most recent).
Prudent Practices in the Laboratory: Handling and Disposal of Chemicals.
Committee on Prudent Practices for Handling, Storage, and Disposal of
Chemicals in Laboratories. National Academy Press, Washington, D.C. 1995
(or the most recent edition).
Facilities/Planning/Physical Plant Design Standards. To be published.
building envelope: the three-dimensional space surrounding a
building containing the building's makeup air.
downwash: pollutants discharged from an exhaust stack that travel
towards the ground due to insufficient discharge velocities, poor wind
dispersion, and physical obstructions.
exhaust air: the air that is removed from an enclosed space and
discharged into atmosphere (ANSI/AIHA Z9.5, 1992).
face velocity: average velocity of air moving perpendicular to
the hood face, usually expressed in feet per minute (fpm) or meter per
second (m/s) (ANSI/ASHRAE 110, 1995)
glove box: a boxlike structure provided with tight-closing doors
or air locks, armholes with impervious gloves sealed to the box at the
armholes, and exhaust ventilation to keep the interior of the box at negative
pressure relative to the surroundings (ANSI/AIHA Z9.5, 1992).
hood face: the plane of minimum area at the front portion of
a laboratory fume hood through which air enters when the sash(es) is (are)
fully opened, usually in the same plane as the sash(es) when sash(es)
is (are) present (ANSI/ASHRAE 110, 1995)
internal condensation: fumes and vapors that condense into liquids
inside of the exhaust stack.
laboratory fume hood: a boxlike structure enclosing a source
of potential air contamination, with one open or partially open side,
into which air is moved for the purpose of containing and exhausting air
contaminants, generally used for bench-scale laboratory operation but
not necessarily involving the use of a bench or a table (ANSI/ASHRAE 110,
1995)
lpm: liters per minute (ANSI/ASHRAE 110, 1995)
makeup air: outside air drawn into a ventilation system to replace
exhaust air (ANSI/AIHA Z9.5, 1992). Makeup air MUST always be provided
when any exhaust system is designed and installed.
perchloric acid hood: a fume hood constructed with water wash
so it is safe for use with perchloric acid or other reagents that might
form flammable or explosive compounds with organic materials of construction
(ANSI/AIHA Z9.5, 1992).
recirculation: air withdrawn from a space, passed through a ventilation
system, and delivered again to an occupied space (ANSI/AIHA Z9.5, 1992).
reentry: The flow of contaminated air that has been exhausted
from a space back into the space through air intakes or openings in the
walls of the space (ANSI/AIHA Z9.5, 1992).
replacement air: see makeup air
return air: air being returned from a space to the ventilation
fan that supplies air to a space (ANSI/AIHA Z9.5, 1992).
special purpose hood: an exhaust hood, not otherwise classified,
for a special purpose such as- but not limited to - capturing gases from
equipment such as atomic absorption, gas chromatographs, liquid pouring
or mixing stations, and heat sources (ANSI/AIHA Z9.5, 1992).
variable air volume fume hood: a fume hood designed so the exhaust
volume is varied in proportion to the opening of the hood face by changing
the speed of the exhaust blower or by operating a damper in the exhaust
hood (ANSI/AIHA Z9.5, 1992).
velocity: speed and direction of motion (ANSI/AIHA Z9.5, 1992).
walk-in hood:a fume hood designed to be floor mounted with sash
and/or doors for closing the open face (ANSI/AIHA Z9.5, 1992).
Applicability: This test is to be conducted when new hoods are
installed or when existing hoods are included as part of a significant
renovation as a condition of acceptance. In addition tests will be conducted
annually or whenever a significant change is made to the operating characteristics
of the hood. Tests to be performed include face velocity measurements
and containment tests.
Test conditions
- General room ventilating systems, both supply and exhaust, including
fume hood exhaust, must meet Facilities Planning Design Specifications
and shall be in full normal operation. Airflow systems in the laboratory
shall be properly balanced and commissioned prior to this test. This
includes calibration of airflow controls, calibration of automatic temperature
controls, balance of supply air, etc. (Prudent Practices for Handling
Hazardous Chemicals in Laboratories, 1995 and ANSI/ASHRAE 110-1995).
Laboratories must be under negative pressure relative to corridor unless
special design conditions prevail.
- Hoods are tested in fully open position, half-open position, and 25%
open position.
- All other hoods in the same room are in half-open position.
- All other hoods on the same floor exhaust system are in half-open
position.
- The hood being tested should be empty.
- The doors to the laboratory will be closed.
- When adjustments are made to hood sashes, supply and exhaust air in
the room will be allowed to stabilize before testing is done.
- Hood monitor is calibrated and not in alarm.
Determination of Average Face Velocity for Variable Air Volume (VAV)Hoods
- The open face of the hood shall be divided into imaginary rectangles
of equal area approximately 1 square foot and velocity shall be measured
in each rectangle.
- Instruments used: Shortridge micromanometer with velgrid
- Average the readings to determine average face velocity
- Note reading of face velocity on Shortridge.
- Average face velocity must be 90-110 fpm at maximum allowed hood opening.
Maximum opening is the point above which the face velocity deteriorates
below 90 fpm.
- Shortridge readings must be within + 20% of the average face velocity.
- Face velocities will also be measured at the one half and one quarter
open positions. The average face velocities at these openings should
be + 10% of the average at the fully open position.
Determination of Average Face Velocity for Constant Air Volume Hoods
- The open face of the hood shall be divided into imaginary rectangles
of equal area approximately 1 square foot and velocity shall be measured
in each rectangle.
Instruments used: Shortridge micromanometer with velgrid Average the
readings to determine average face velocity
- Note reading of face velocity on Shortridge.
- Average face velocity must be 90-110 fpm at the one-half open position.
- Shortridge readings must be within + 20% of the average face velocity.
Smoke Testing To Determine Direction of Airflow and Air Turbulence and
Contaminant Reentry
- Using a smoke tube, puff smoke 6 inches within the face of the hood
around the outside edge of the opening. Determine direction of smoke
flow. If visible fumes flow out of the front of the hood, make necessary
adjustments.
- Ignite a smoke candle in the hood and visually observe if there is
leakage of smoke from the ductwork or if smoke is being drawn back into
building or surrounding buildings.
Conditions For Passing Hoods
- General room ventilating systems, both supply and exhaust, including
fume hood exhaust shall be in full normal operation.
- Hood must have an acceptable face velocity and must pass the smoke
testing.
- No leakage of exhaust from ductwork and no reentry of hood exhaust
into buildings
Applicability: This test is to be conducted annually to check
the performance of established fume hoods or whenever a significant change
is made to the operating characteristics of the hood. Tests to be performed
include face velocity measurements and containment tests.
Test conditions
- General room ventilating systems, both supply and exhaust, including
fume hood exhaust shall be in full normal operation. Laboratories must
be under negative pressure relative to corridor unless special design
conditions prevail.
- Hoods are tested in fully open position, the half- open position,
and 25% open position.
- All other hoods in the same room are in the half-open position.
- All other hoods on the same floor exhaust system are half-open position.
- The hood being tested must be empty.
- The doors to the laboratory will be closed.
- When adjustments are made to hood sashes, supply and exhaust air in
the room will be allowed to stabilize before testing is done.
- Hood monitor is calibrated and not in alarm.
Determination of Average Face Velocity for Variable Air Volume (VAV)Hoods
- The open face of the hood shall be divided into imaginary rectangles
of equal area approximately 1 square foot and velocity shall be measured
in each rectangle.
- Instruments used: Shortridge micromanometer with velgrid
- Average the readings to determine average face velocity
- Note reading of face velocity on Shortridge.
- Average face velocity must be 90-110 fpm at maximum allowed hood opening.
Maximum opening is the point above which the face velocity deteriorates
below 90 fpm.
- Shortridge readings must be within + 20% of the average face velocity.
- Face velocities will also be measured at the one half and one quarter
open positions. The average face velocities at these openings should
be + 10% of the average at the fully open position.
Determination of Average Face Velocity for Constant Air Volume Hoods
- The open face of the hood shall be divided into imaginary rectangles
of equal area approximately 1 square foot and velocity shall be measured
in each rectangle.
- Instruments used: Shortridge micromanometer with velgrid
- Average the readings to determine average face velocity
- Note reading of face velocity on Shortridge.
- Average face velocity must be 90-110 fpm at the one-half open position
or as a minimum at the operational position of 14 inches.
- Shortridge readings must be within + 20% of the average face velocity.
Smoke Testing To Determine Direction of Airflow, Air Turbulence, and
Reentry of Contaminants
- Using a smoke tube, puff smoke 6 inches within the face of the hood
around the outside edge of the opening. Determine direction of smoke
flow. If visible fumes flow out of the front of the hood, make necessary
adjustments.
Additional Smoke Testing to Determine Reentrainment
This testing will be conducted whenever a significant change is made
to the fume hood system or if problems have been noted.
- Ignite a smoke candle in the hood and visually observe if there is
leakage of smoke from the ductwork or if smoke is being drawn back into
building or surrounding buildings.
Conditions For Passing Hoods
- General room ventilating systems, both supply and exhaust, including
fume hood exhaust shall be in full normal operation.
- Hood must have an acceptable face velocity and must pass the smoke
testing.
- There must be no leakage of exhaust from ductwork and no reentry of
hood exhaust into buildings
Environmental Health and Safety
- Inspects the entire fume hood operating systems including the fume
hood, associated duct work, exhaust blowers, and stacks
- Places a sticker on fume hoods with average face velocity if the hood
operating systems "PASS"
- Places a "DO NOT USE" sign on the hood sash if the hood operating
system does "NOT PASS"
- Puts in a work order on behalf of the department head to Physical
Plant for repair
- Notifies the Department Head, Department Health and Safety Coordinator,
Physical Plant, and Facilities Planning of any hoods which are placed
"OUT OF SERVICE"
Physical Plant and Facilities Planning
- Make all necessary repairs/modifications, in a timely manner, to the
fume hood operating system, and any associated equipment which affects
the fume hood operating system in order to make the entire system safe
to use
- Notify Environmental Health and Safety (EH&S)after all repairs/modifications
are completed. EH&S will then retest the system.
- Notify EH&S on a monthly basis in writing as to the status of repair/replacement
of fume hoods based on work orders/work requests submitted.
Department Head
- Ensure that any fume hoods which are placed "OUT OF SERVICE" will
not be used until notified by EH&S that the hood can be used.
- Ensure that repairs/modifications are completed in a timely manner
to any fume hoods which have been placed "OUT OF SERVICE"
- Notify EH&S and Physical Plant of any fume hoods which are not operating
properly
Personnel Using Fume Hoods
- Follow all safety and health procedures specified in the Laboratory
Health and Safety Manual and by the faculty supervisor in the laboratory
- Attend all required health and safety training sessions
- Do not use fume hoods which are "OUT OF SERVICE"
- Report fume hoods which are not operating properly, accidents, unhealthy,
and unsafe conditions to the faculty supervisor
- Notify faculty supervisor of any pre-existing health conditions that
could lead to serious health situations when using a fume hood.
|
Appendix G
|
|
WARNING
DO NOT USE
|
|
Building:
|
Date:
|
|
Room:
|
Hood #
|
|
Inspector:
|
Repair Tag #:
|
|
Work Order #
(Note: Call in under ACTION CODE 24)
|
Date Submitted:
|
|
This fume hood was tested for performance but was
found to be
OUT OF SERVICE
for the following reasons:
|
|
.
|
|
Physical Plant personnel have been
notified, and will make the necessary repairs.
DO NOT remove this sign or use
the fume hood until it has been re-tested by
Environmental Health and Safety.
For more information, call Physical Plant
Customer Service at 5-0600 or Environmental
Health and Safety at 5-2682.
|
|
Physical Plant Personnel
Tear off at perforation and return
to EH&S for hood performance re-evaluation
|
|
PHYSICAL PLANT USE ONLY
|
|
Building:
|
Room #:
|
|
Hood #:
|
Date Repaired:
|
|
Work Order #:
|
Comments:
|
|
Physical Plant Technician:
|
|